首页> 外文会议>2016 IEEE International Conference on Power System Technology >Composite system adequacy assessment incorporating virtual power plants
【24h】

Composite system adequacy assessment incorporating virtual power plants

机译:包含虚拟电厂的综合系统充分性评估

获取原文
获取原文并翻译 | 示例

摘要

A systematic procedure for assessing composite system adequacy of power systems incorporating Virtual Power Plants (VPP) is introduced in this paper. The VPP model used in this research work represents an aggregated profile of numerous Distributed Energy Resources together with loads belonging to a specified distribution network. The VPP's performance is evaluated using two new indices - Mean VPP Export (External) and Expected VPP Energy Not Used (External) - defined in this paper. A linearized DC load flow based optimal power flow formulation is introduced as part of the overall proposed composite system adequacy assessment procedure, and the impacts of the VPP's incorporation on reliability at the system and at individual transmission bus levels are quantified. Impacts of variations in parameters like the VPP's point of connection to the transmission grid, forced outage rates of transmission lines, etc., on the VPP's performance metrics are also addressed.
机译:本文介绍了一种评估包含虚拟电厂(VPP)的电力系统综合系统充分性的系统程序。本研究工作中使用的VPP模型代表了众多分布式能源资源的汇总配置文件,以及属于指定配电网络的负荷。 VPP的性能通过本文定义的两个新指标进行评估-平均VPP出口(外部)和未使用的预期VPP能源(外部)。在整个拟议的复合系统充分性评估程序中,引入了基于线性化直流潮流的最佳潮流公式,并量化了VPP的引入对系统和各个传输总线级别的可靠性的影响。还解决了参数变化(例如VPP到传输网格的连接点,传输线的强制中断率等)对VPP性能指标的影响。