IEEE Std. 998-2012 is an industry standard guideline for designing lightning protection systems for high voltage (HV) substations. It describes the use of an Electrogeometric model (EGM) for design and provides an equation for the approximation of the allowable stroke current. The stroke current is used to determine a strike distance for the substation lightning protection system. The allowable stroke current equation is a function of the surge impedance of the busbar and the Basic Insulation Level (BIL) of the equipment. The equation does not take into account the substation's surge arresters which will limit the overvoltages within the substation. This report discusses how an Electromagnetic Transient (EMT) model can be used to estimate an allowable stroke current through consideration of the substation plant and arrangement. An example is provided to show how an EGM and an EMT model can be combined to calculate a striking distance that meets designed Mean Time Between Failures (MTBF).
机译:IEEE标准998-2012是用于设计高压(HV)变电站的雷电保护系统的行业标准指南。它描述了在设计中使用电几何模型(EGM)的方法,并提供了近似的允许冲程电流的方程式。行程电流用于确定变电站防雷系统的触击距离。允许的行程电流公式是母线的浪涌阻抗和设备的基本绝缘水平(BIL)的函数。该方程式未考虑变电站的电涌放电器,后者会限制变电站内的过电压。本报告讨论了如何通过考虑变电站的布置和布置,使用电磁暂态(EMT)模型来估算允许的行程电流。提供了一个示例来说明如何将EGM和EMT模型结合起来以计算满足设计平均故障间隔时间(MTBF)的打击距离。