首页> 外文会议>Down to Earth Conference >Lightning protection of substations using EMT modelling
【24h】

Lightning protection of substations using EMT modelling

机译:使用EMT建模的变电站雷电保护

获取原文

摘要

IEEE Std. 998-2012 is an industry standard guideline for designing lightning protection systems for high voltage (HV) substations. It describes the use of an Electrogeometric model (EGM) for design and provides an equation for the approximation of the allowable stroke current. The stroke current is used to determine a strike distance for the substation lightning protection system. The allowable stroke current equation is a function of the surge impedance of the busbar and the Basic Insulation Level (BIL) of the equipment. The equation does not take into account the substation's surge arresters which will limit the overvoltages within the substation. This report discusses how an Electromagnetic Transient (EMT) model can be used to estimate an allowable stroke current through consideration of the substation plant and arrangement. An example is provided to show how an EGM and an EMT model can be combined to calculate a striking distance that meets designed Mean Time Between Failures (MTBF).
机译:IEEE STD。 998-2012是一种用于为高电压(HV)变电站的防雷系统设计避雷系统的行业标准指南。它描述了用于设计的电幂型模型(EGM)的用途,并提供用于近似允许行程电流的等式。行程电流用于确定变电站防雷系统的撞击距离。允许行程电流等式是汇流条的浪涌阻抗和设备的基本绝缘水平(BIL)的函数。该等式没有考虑到变电站的浪涌避雷器,这将限制变电站内的过电压。本报告讨论了如何使用电磁瞬态(EMT)模型通过考虑变电站植物和布置来估计允许的行程电流。提供了一个示例以示出EGM和EMT模型如何组合以计算满足故障(MTBF)之间设计平均时间的醒目距离。