The use of earthing in electrical power reticulation has an interesting history. Initial power distribution systems did not deliberately reference the phase conductors to earth. Later, depending on the application, there was a bifurcation of earthing practices, with some systems solidly earthed through low impedance resistors and some loosely earthed through high impedance resistors. The coal mining industry in Australia has converged to high resistance earthing. The supply is removed on the first earth fault to ensure that the fault is not escalated on the occurrence of a second earth fault. While this has safety benefits, there are challenges for the design of sensitive earth leakage protection. This is further complicated with the introduction of Variable Speed Drives (VSDs). This paper charts the history of earthing and how it has influenced the way that earth fault protection is implemented in coal mines, both in Australia and overseas.
机译:在电力网状结构中使用接地已有一段有趣的历史。最初的配电系统没有故意将相线接地。后来,根据应用的不同,接地方式出现了分歧,一些系统通过低阻抗电阻器牢固地接地,有些系统通过高阻抗电阻器牢固地接地。澳大利亚的煤炭开采业已融合到高电阻接地。在第一个接地故障时断开电源,以确保在第二个接地故障发生时故障不会升级。尽管这样做具有安全性,但是设计灵敏的漏电保护装置仍存在挑战。随着变速驱动器(VSD)的引入,情况变得更加复杂。本文概述了接地的历史以及它如何影响澳大利亚和海外煤矿的接地保护的实施方式。