摘要

Constant growth of distributed generation (DG) in power systems has not only positive changes. Incorrect placement of DG can worsen steady-state parameters of a power grid, for example, power losses. The specific method of optimal DG placement and capacity, that has been developed previously, was improved. Now method determines the effect of installed DG on the power grid operation considering type and capacity of DG units, climatic pattern of installation region and different power grid steady-states. Method improvements have been tested on IEEE 14-bus test system using Monte-Carlo method. The results of simulation tests show viability of the updated method.
机译:电力系统中分布式发电(DG)的不断增长不仅带来了积极的变化。 DG的不正确放置会恶化电网的稳态参数,例如功率损耗。之前已经开发出了优化最佳DG放置和容量的方法。现在,该方法根据DG单元的类型和容量,安装区域的气候模式以及不同的电网稳态来确定已安装的DG对电网运行的影响。方法改进已使用蒙特卡洛方法在IEEE 14总线测试系统上进行了测试。仿真测试结果表明了该方法的可行性。