Modelling of upward leader inception is important for calculating lightning shielding failure rates of transmission lines. The leader inception model proposed by Gallimberti I. has been widely adopted for about 30 years and applied in the analysis of unstable upward leader inception. However, the gas kinetic process and heat transfer via conduction are not considered in this model. Theoretical analysis and simplified simulation show that the gas density variation and heat conduction cannot be neglected. In this paper, the gas kinetics and heat conduction have been considered, and a simplified one-dimensional thermofluid dynamics (1D-TFD) model has been proposed as an upward leader inception criterion. A Mach-Zehnder interferometer was set up to observe the gas density variation in leader channel and the channel expansion. Experimental results indicate that the gas density reduction in leaders is significant, and the calculation of the channel diameter expansion has a good agreement with that obtained by experiments.
机译:向上引导起始点的建模对于计算传输线的雷电屏蔽故障率很重要。 Gallimberti I.提出的领导者起始模型已被广泛采用约30年,并被用于不稳定的向上领导者起始分析中。但是,该模型未考虑气体动力学过程和通过传导的热传递。理论分析和简化模拟表明,气体密度变化和热传导不能忽略。在本文中,考虑了气体动力学和热传导,并提出了简化的一维热流体动力学(1D-TFD)模型作为向上的先导判据。设置了一个Mach-Zehnder干涉仪,以观察引导通道和通道扩展中的气体密度变化。实验结果表明,引气管中气体密度的降低是显着的,通道直径膨胀的计算结果与实验结果吻合良好。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号