Experimental study of overvoltage on distribution lines induced by artificially rocket-triggered lightning

机译:火箭触发雷电引起配电线路过电压的实验研究

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

Lightning induced overvoltage is the important reason for the insulation flashover of power distribution line. In order to reduce the lightning accident and to improve the power supply reliability of the distribution network, it is of outstanding significance for engineering purposes to study the lightning current and induced overvoltage on distribution lines. So a 280 meter-long 10 kV power distribution experimental line has been established in Guangzhou which is the most frequently-occurred area of thunderstorms in China. Therefore, the experiment platform is set up to measure overvoltage and the current is measured by Rogowski coils. All the measured lightning currents are accompanied by return-stroke process for many times, which the amplitude of initial lightning current is between -22.5~35.4 kA and the peak of the return-stroke current is between -40.8~24.2 kA. And the data of the lightning induced overvoltage on 10kV distribution line has been acquired four times. After analysis, the empirical formula of calculating overvoltage induced by rocket-triggered lightning is in the range of the error of the engineering application.
机译:雷电感应过电压是配电线路绝缘闪络的重要原因。为了减少雷击事故并提高配电网的供电可靠性,研究配电线路的雷电流和感应过电压对工程具有重要意义。因此,在广州建立了一条280米长的10 kV配电实验线,这是中国雷暴最频繁的地区。因此,建立了实验平台以测量过电压,并通过Rogowski线圈测量电流。所有测得的雷电流都多次伴随着回程过程,其初始雷电流的幅度在-22.5〜35.4 kA之间,回程电流的峰值在-40.8〜24.2 kA之间。并获得了10kV配电线路雷电感应过电压的数据四次。经过分析,计算火箭触发雷击产生的过电压的经验公式在工程应用误差范围内。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号