首页> 外文会议>Intemational Conference of Lighbling Protection >Experimental study of overvoltage on distribution lines induced by artificially rocket-triggered lightning
【24h】

Experimental study of overvoltage on distribution lines induced by artificially rocket-triggered lightning

机译:人工火箭触发闪电引起的过电压过电压的实验研究

获取原文

摘要

Lightning induced overvoltage is the important reason for the insulation flashover of power distribution line. In order to reduce the lightning accident and to improve the power supply reliability of the distribution network, it is of outstanding significance for engineering purposes to study the lightning current and induced overvoltage on distribution lines. So a 280 meter-long 10 kV power distribution experimental line has been established in Guangzhou which is the most frequently-occurred area of thunderstorms in China. Therefore, the experiment platform is set up to measure overvoltage and the current is measured by Rogowski coils. All the measured lightning currents are accompanied by return-stroke process for many times, which the amplitude of initial lightning current is between -22.5~35.4 kA and the peak of the return-stroke current is between -40.8~24.2 kA. And the data of the lightning induced overvoltage on 10kV distribution line has been acquired four times. After analysis, the empirical formula of calculating overvoltage induced by rocket-triggered lightning is in the range of the error of the engineering application.
机译:闪电引起的过电压是配电线绝缘闪光灯的重要原因。为了减少闪电事故并提高分销网络的电力供应可靠性,对工程目的具有出色的重要性,以研究雷电流和诱导分配线上的过电压。因此,广州建立了280米长的10千伏配电实验线,这是中国最常见的雷暴领域。因此,实验平台设置为测量过电压,电流由Rogowski线圈测量。所有测量的雷电电流都伴随着返回行程过程多次,初始雷电流的幅度在-22.5〜35.4ka之间,返回行程电流的峰值在-40.8〜24.2ka之间。并且雷电引起的10kV配电线上的过电压已经获得了四次。在分析之后,通过火箭触发闪电诱导计算过电压的经验公式是工程应用误差的范围。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号