Liquid nitrogen is often used in superconducting high voltage apparatus for cooling and for electrical insulation purposes. A temperature increase of the superconductor surface, e. g. to room temperature during a quench of a fault current limiter, may cause a decrease of the breakdown voltage within the apparatus by generation of nitrogen gas bubbles. A cryostat was equipped with a sphere to plane electrode arrangement with adjustable gap for the examination of the breakdown and withstand voltages of liquid nitrogen. Bubble generation of the heatable plane was verified by camera observation. Alternating voltage up to 230 kVrms was applied to the arrangement under the pressure condition of 0.1 MPa (absolute). Degradation of the withstand voltage up to 50% was found by using a 500 W heater in comparison to the case with no heating.
机译:液氮通常用于超导高压设备中以进行冷却和电绝缘。超导体表面的温度升高,例如。 G。在故障限流器失超的过程中,如果温度升至室温,可能会由于氮气气泡的产生而导致设备内的击穿电压降低。低温恒温器配有球面电极和可调节间隙的平面电极装置,用于检查液氮的击穿和耐压。通过照相机观察验证了可加热平面的气泡的产生。在0.1 MPa(绝对压力)的压力条件下,将最高230 kVrms的交流电压施加到该装置。与不加热的情况相比,使用500 W的加热器发现耐压下降了50%。