Improved inter-area stability using an LQG controller incorporating synchrophasor data

机译:使用包含同步相量数据的LQG控制器提高了区域间稳定性

获取原文
获取原文并翻译 | 示例

摘要

There has been a recent increase in the deployment of phasor measurement units (PMUs) based on the IEEE C37.118 standard. Also referred to as synchrophasors, these have enabled the use of real-time frequency and frequency-rate measurements from generators and substations to be included in load-frequency control applications. This paper presents a method for improving the frequency damping characteristics of a three-area system that experiences 0.5 Hz oscillations. A linear quadratic Gaussian (LQG) controller is developed that includes a Kalman filter for the unmeasured states. An inter-area damping controller is developed using frequency measurements at a sample rate and resolution that would be achieved with IEEE C37.118 compliant synchrophasors in each of the three areas. Simulation results demonstrate the effectiveness of the proposed controller under realistic circumstances.
机译:最近基于IEEE C37.118标准的相量测量单元(PMU)的部署有所增加。这些也被称为同步相量,它们使得能够将来自发电机和变电站的实时频率和频率速率测量结果用于负载频率控制应用中。本文提出了一种改善具有0.5 Hz振荡的三区域系统的频率阻尼特性的方法。开发了一种线性二次高斯(LQG)控制器,该控制器包括用于未测状态的卡尔曼滤波器。区域间阻尼控制器是使用采样率和分辨率的频率测量来开发的,这将通过三个区域中每个区域中符合IEEE C37.118的同步相量来实现。仿真结果证明了所提出的控制器在实际情况下的有效性。