Firefighter safety for PV systems: Overview of future requirements and protection systems

机译:光伏系统的消防员安全:未来要求和保护系统概述

获取原文
获取原文并翻译 | 示例

摘要

An important and highly discussed safety issue for photovoltaic systems is that, as long as they are illuminated, a high voltage is present at the PV string terminals and cables between the string and inverters, independent of the state of the inverter's dc disconnection switch, which poses a risk for operators during maintenance or fire-fighting. One of the solutions is individual module shutdown by short-circuiting or disconnecting each PV module from the PV string. However, currently no standards have been adopted either for implementing or testing these methods, or doing an evaluation of the module shutdown procedures. This paper gives an overview on the most recent fire — and firefighter safety requirements for PV systems, with focus on system and module shutdown systems. Several solutions are presented, analyzed and compared by considering a number of essential characteristics, including their transient behavior, components' voltage stress and conduction losses.
机译:光伏系统的一个重要且受到广泛讨论的安全问题是,只要光伏系统被照亮,光伏串的端子和串与逆变器之间的电缆就会出现高压,而与逆变器的直流断开开关的状态无关。在维护或灭火过程中会对操作人员造成危险。解决方案之一是通过将每个PV模块与PV串短路或断开连接来单独关闭模块。但是,目前尚未采用任何标准来实施或测试这些方法,或对模块关闭程序进行评估。本文概述了光伏系统的最新消防和消防员安全要求,重点是系统和模块关闭系统。通过考虑许多基本特性,包括瞬态行为,组件的电压应力和传导损耗,提出,分析和比较了几种解决方案。