首页> 外文会议>2012 Sixth IEEE/PES Transmission and Distribution: Latin America Conference and Exposition. >Diagnosis of power transformers through frequency response analysis by poles and zeros shifts identification
【24h】

Diagnosis of power transformers through frequency response analysis by poles and zeros shifts identification

机译:通过零频点和零频点识别的频率响应分析诊断电力变压器

获取原文
获取原文并翻译 | 示例

摘要

Detection of abnormalities within transformers is a field of study aimed at preventing future permanent damage. Current automatic diagnosis methodologies include some proposals that use the Sweep Frequency Response Analysis (SFRA) technique as a condition assessment criterion. SFRA has a high sensitivity to various failures in windings and iron core. However, these methodologies are not completely robust due to the parameters used for discrimination, generally statistical indicators. This paper shows a new diagnosis methodology, which has been successfully applied in other fields, based on Vector Fitting analysis for poles and zero shifts recognition. Vector Fitting is a suitable tool as a condition assessment in SFRA traces analysis, where the analysis is done using poles and zeros location of the transfer function. As poles and zeros are represented in complex domain, the Principal Component Analysis (PCA) is introduced for data complex transformation to the real domain with the same information.
机译:变压器内部异常的检测是旨在防止将来永久损坏的研究领域。当前的自动诊断方法包括一些使用扫描频率响应分析(SFRA)技术作为条件评估标准的建议。 SFRA对绕组和铁芯的各种故障具有很高的敏感性。但是,由于用于区分的参数(通常是统计指标),这些方法并不完全可靠。本文展示了一种新的诊断方法,该方法已基于矢量拟合分析的极点和零偏移识别而成功应用于其他领域。矢量拟合是SFRA迹线分析中作为状态评估的一种合适工具,该分析使用传递函数的零点和零点位置进行。由于极点和零点在复杂域中表示,因此引入了主成分分析(PCA),以将具有相同信息的数据复杂转换为实域。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号