It is rare for modern power cables to use a solid, continuous screen in their construction. For reasons of economy and ease of construction modern cables increasingly use screens comprised of sparsely spaced conductors. The electrical relationship between a screen manufactured using this construction and the core it surrounds is markedly different to the relationship between a solid coaxial screen and the core it surrounds. The ability of a cable screen to return current during a fault situation is significantly dependent on its relationship with the core carrying the fault energy and has significant impact on the performance of the earthing systems involved. This paper examines how different the performance of the sparsely screened cables is to their solidly screened predecessors.
机译:现代电力电缆很少在其结构中使用坚固,连续的屏蔽层。出于经济和易于构造的原因,现代电缆越来越多地使用由稀疏间隔的导体组成的屏蔽层。用这种结构制造的屏幕与它所包围的芯之间的电气关系与实心同轴屏幕和它所包围的芯之间的电气关系明显不同。电缆屏蔽层在故障情况下返回电流的能力在很大程度上取决于其与承载故障能量的芯线之间的关系,并对所涉及的接地系统的性能产生重大影响。本文研究了稀疏屏蔽的电缆与其坚固屏蔽的电缆的性能有何不同。