首页> 外文会议>2012 6th Asia-Pacific Conference on Environmental Electromagnetics. >Analysis on influence of tall tower on lightning current measurement
【24h】

Analysis on influence of tall tower on lightning current measurement

机译:高塔对雷电流测量的影响分析

获取原文
获取原文并翻译 | 示例

摘要

Most of the measurements of nature lightning current time-domain waveforms were taken at the tall towers and tall buildings. In order to study the influence of tall towers on lightning current measurement, the transmission line (TL) model of the lightning return stroke was applied to calculate the lightning current at different positions of the tower. This paper also analyzed the factors which influence the results of lightning current measurement on tall towers. Simulation result shows that the current obtained at the top of the tower is most close to the real lightning current, and the amplitude of lightning current is influenced by a few factors, such as the height of the tower, the reflectance of the ground and the rise-time of the lightning current waveform. However, the lightning current waveforms measured at different positions of low towers are almost the same.
机译:自然闪电电流时域波形的大多数测量是在高层塔楼和高层建筑物上进行的。为了研究高塔对雷电流测量的影响,应用了雷击回程的传输线(TL)模型来计算塔不同位置的雷电流。本文还分析了影响高塔雷电测量结果的因素。仿真结果表明,塔顶获得的电流最接近真实雷电电流,雷电流的幅度受塔高,地面反射率和反射率等因素的影响。雷电电流波形的上升时间。但是,在低塔的不同位置处测得的雷电流波形几乎相同。