摘要

Local thermal hot-spots in microprocessors lead to worst-case provisioning of global cooling resources, especially in large-scale systems where cooling power can be 50∼100% of IT power. Further, the efficiency of cooling solutions degrade non-linearly with supply temperature. Recent advances in active cooling techniques have shown on-chip thermoelectric coolers (TECs) to be very efficient at selectively eliminating small hot-spots. Applying current to a superlattice TEC-film that is deposited between silicon and the heat spreader results in a Peltier effect, which spreads the heat and lowers the temperature of the hot-spot significantly and improves chip reliability. In this paper, we propose that hot-spot mitigation using thermoelectric coolers can be used as a power management mechanism to allow global coolers to be provisioned for a better worst case temperature leading to substantial savings in cooling power. In order to quantify the potential power savings from using TECs in data center servers, we present a detailed power model that integrates on-chip dynamic and leakage power sour-ces, heat diffusion through the entire chip, TEC and global cooler efficiencies, and all their mutual interactions. Our multi-scale analysis shows that, for a typical data center, TECs allow global coolers to operate at higher temperatures without degrading chip lifetime, and thus save ∼27% cooling power on average while providing the same processor reliability as a data center running at 288K.
机译:微处理器中的局部热点导致在最坏情况下配置全局冷却资源,尤其是在大型系统中,冷却功率可能是IT功率的50%至100%。此外,冷却溶液的效率随供应温度呈非线性下降。主动冷却技术的最新进展表明,片上热电冷却器(TEC)在选择性消除小热点方面非常有效。向沉积在硅和散热器之间的超晶格TEC膜施加电流会产生珀尔帖效应,该效应会扩散热量并显着降低热点温度,并提高芯片可靠性。在本文中,我们建议使用热电冷却器的热点缓解措施可以用作电源管理机制,以便为全局冷却器提供更好的最坏情况温度,从而大大节省冷却功率。为了量化在数据中心服务器中使用TEC可能节省的电量,我们提出了一个详细的功耗模型,该模型集成了片上动态和泄漏功率源,整个芯片的散热,TEC和全局冷却器效率,以及所有他们彼此的互动。我们的多尺度分析表明,对于典型的数据中心而言,TEC使全局冷却器能够在更高的温度下运行而不会降低芯片寿命,从而平均节省了约27%的冷却功率,同时提供了与数据中心运行的数据中心相同的处理器可靠性。 28.8万

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号