首页> 外文会议>2003 Stewardship of drinking water quality >Designing Ozone Systems for Cryptosporidium Inactivation:Evaluating Impacts of New EPA CT Requirements
【24h】

Designing Ozone Systems for Cryptosporidium Inactivation:Evaluating Impacts of New EPA CT Requirements

机译:设计用于隐孢子虫灭活的臭氧系统:评估新EPA CT要求的影响

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

The impacts of new CT requirements for ozone disinfection of Cryptosporidium are evaluatedrnusing a desktop CT disinfection analysis. The analysis is applied to the design of new andrnupgraded ozone systems for two water treatment plants in Virginia. The results indicate that thernfeasibility of ozone disinfection of Cryptosporidium is dependent on ozone demand and decayrncharacteristics of the water supply and may not be feasible for water supplies with moderate tornhigh ozone decay rates. The CT analysis is a useful design procedure to evaluate the benefit-costrntradeoffs of using ozone to achieve alternative disinfection goals.
机译:使用台式CT消毒分析评估了新的CT要求对隐孢子虫进行臭氧消毒的影响。该分析被应用于弗吉尼亚州两个水处理厂新的和升级的臭氧系统的设计。结果表明,对隐孢子虫进行臭氧消毒的可行性取决于臭氧的需求和供水的衰减特性,对于中等程度高的臭氧衰减率的供水可能不可行。 CT分析是一种有用的设计程序,可用于评估使用臭氧实现替代消毒目标的收益-成本之间的权衡。