首页> 外文会议>International offshore and polar engineering conference;ISOPE 2004 >Maximum Withstand Voltage of Artificial Ice-covered Insulators
【24h】

Maximum Withstand Voltage of Artificial Ice-covered Insulators

机译:人造覆冰绝缘子的最大耐压

获取原文
获取原文并翻译 | 示例

摘要

This paper introduces the functions and characteristics ofrnthe newly built multifunction artificial climate chamber of ChongqingrnUniversity. Based on the test results performed on several types of icedrninsulators with a withstand voltage method in the chamber, it indicatesrnthat the withstand duration for an iced insulator should be at least 15rnminutes, and that at normal conditions, all the tested insulator stringsrniced with a freezing water conductivity of 300μS/cm can withstand thernservice voltage. It analyzes the effect of the atmospheric pressure onrnwithstand and flashover voltages. Because the discharge path has a highrnrandomness, the effect of atmospheric pressure on flashover voltages ofrniced insulators has a high disparity.
机译:介绍了重庆大学新建的多功能人工气候箱的功能和特点。根据对几种类型的冰绝缘子在试验箱中采用耐压方法进行的测试结果,它表明,冰绝缘子的绝缘持续时间应至少为15分钟,并且在正常条件下,所有测试过的绝缘子都用冷冻水进行了麻花形处理。电导率300μS/ cm可以承受工作电压。它分析了大气压对耐压和闪络电压的影响。由于放电路径具有较高的随机性,因此大气压对带电绝缘子的闪络电压的影响存在很大差异。