摘要

A 6.6 kV continuous disc type winding of a distribution transformer is used to investigate the propagation of partial discharges (PD) with the aim of location. The winding was modelled, as multiconductor transmission lines with each turn represented by a transmission line. This approach results in the model being valid up to a few MHz in frequency. The validity of the model was confirmed by impedance measurements on the winding. The transfer functions calculated between probable PD source locations to winding terminals showed that the troughs (or zeros) change in frequency with the location of PD source and hence can be used for the location of PD. Transfer functions obtained experimentally using a discharge calibrator as the PD source, showed very good agreement with the calculations.
机译:配电变压器的6.6 kV连续盘形绕组用于研究局部放电(PD)的传播,以进行定位。将绕组建模为多导体传输线,每匝由传输线表示。这种方法导致模型在高达几个MHz的频率上有效。该模型的有效性通过绕组上的阻抗测量得到了证实。计算出的可能的PD源位置到绕组端子之间的传递函数表明,波谷(或零点)的频率随PD源的位置而变化,因此可用于PD的位置。使用放电校准器作为PD源,通过实验获得的传递函数与计算结果非常吻合。