摘要

The greenhouse effect of SF6 has made its application in various types of gas-insulated equipment increasingly restricted. C6F12O combines the advantages of insulation strength, safety and environmental friendliness and is considered to have potential for use in medium and low voltage equipment when mixed with buffer gas. In this paper, an experimental study on the partial discharge characteristics of C6F12O/CO2 mixed gas was carried out. The partial discharge initial voltage and the partial discharge extinction voltage of the mixed gas under the power frequency voltage are measured, and compared with the breakdown voltage. It was found that the partial discharge initiation voltage and the extinction voltage of the mixed gas gradually increased with the mixing ratio, and the influence of the gas pressure on the high mixing ratio was large. Compared with pure CO2, the difference between the partial discharge starting voltage and the breakdown voltage of the mixed gas is large. The research in this paper can provide guidance for the operation and maintenance of C6F12O mixed gas in the application of medium and low voltage equipment.
机译:SF6的温室效果使其在各种类型的气体绝缘设备中的应用越来越受限制。 C6F12O结合了绝缘强度,安全性和环境友好的优点,并且被认为具有与缓冲气体混合时在中低压设备中使用的潜力。本文进行了对C6F12O / CO2混合气体的局部放电特性的实验研究。测量局部放电初始电压和在功率频率电压下的混合气体的局部放电消光电压,并与击穿电压进行比较。发现局部放电启动电压和混合气体的消光电压随混合比逐渐增加,气体压力对高混合比的影响大。与纯二氧化碳相比,混合气体的局部放电启动电压和击穿电压之间的差异很大。本文的研究可以为介质和低压设备应用C6F12O混合气体的操作和维护提供指导。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号