An Economic Analysis of Air-Conditioning Systems with Off-Peak Chilled-Water Storage

机译:非峰值冷冻水储存空调系统的经济性分析

获取原文

摘要

This thesis investigates current methods of chilled-water storage for air conditioning applications and the economics of chilled-water storage with time-of-use electric utility rates. Current methods of chilled-water storage are investigated by comparing costs of construction materials for storage tanks and effectiveness and costs of anti-blending systems. The economics of chilled-water storage are analyzed by computing total life cycle costs of alternative air conditioning systems for two different sized buildings. Computer simulation is used to determine electric consumption for the buildings. The simulation of each building contains three options: no chilled-water storage, chiller operated only at night, and a small chiller supplemented by stored chilled-water. A gunite or styrofoam tank with a moving partition anti-blending system is the least expensive and most effective storage system. The economics of chilled-water storage are sensitive to the size of the building analyzed. Operating the small chiller with supplemental chilled-water is economical in the smaller building. No chilled-water storage is the most economical option in the larger building. Operation of the chiller only at night was never economical. (Author)