首页> 外文期刊>Engineering failure analysis >Failure analysis of cupronickel evaporator tubes of a chilling plant
【24h】

Failure analysis of cupronickel evaporator tubes of a chilling plant

机译:某冷库白铜蒸发器管的失效分析

获取原文
获取原文并翻译 | 示例
           

摘要

Pin-hole leakage was observed in a number of 90/10 cupronickel evaporator tubes of a chilling plant which was in service for about 6 years. Chilled water is cooled from 12 deg C to 7 deg C which flows inside the evaporator tubes, while the OD side has LiBr environment. The failure investigation of the failed tubes revealed greenish/blackish uniform deposits together with some spots where localized thick deposits on the ID surfaces were present. Underdeposit corrosion beneath these thick deposits was the primary reason for failure of the tubes. Intergranular corrosion was also observed underneath the thick deposits. The ID surface of the failed tubes confirmed the presence of wide variety of deposits, e.g. carbonates, silicates, phosphates, and sulphur-bearing compounds. The stagnant conditions under the thick deposits alter the chemistry inside the crevices thus formed. The altered chemistry conditions caused rapid corrosion (and intergranular attack) on the cupronickel tubes. Remedial measures that may be undertaken to prevent future occurrence of the problem are addressed.
机译:在使用了大约6年的冷却设备的许多90/10铜镍合金蒸发器管中观察到针孔泄漏。冷却水从12摄氏度冷却到7摄氏度,在蒸发器管内流动,而OD侧具有LiBr环境。失效管的失效研究表明,带绿色/黑色均匀沉积物,以及在ID表面上存在局部较厚沉积物的一些斑点。这些厚的沉积物下面的沉积物不足是管子失效的主要原因。在厚的沉积物下面也观察到晶间腐蚀。失效管的内径表面证实存在各种沉积物,例如沉积物。碳酸盐,硅酸盐,磷酸盐和含硫化合物。厚沉积物的停滞状态改变了如此形成的缝隙内部的化学性质。化学条件的改变导致了白铜管的快速腐蚀(和晶间腐蚀)。解决了可以采取的预防措施,以防止将来再次出现此问题。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号