首页> 外文期刊>International Journal of Refrigeration >HFO1234ze(E) vaporisation inside a Brazed Plate Heat Exchanger (BPHE): Comparison with HFC134a and HFO1234yf
【24h】

HFO1234ze(E) vaporisation inside a Brazed Plate Heat Exchanger (BPHE): Comparison with HFC134a and HFO1234yf

机译:钎焊板式换热器(BPHE)中的HFO1234ze(E)汽化:与HFC134a和HFO1234yf的比较

获取原文
获取原文并翻译 | 示例

摘要

This paper investigates the effects of heat flux, saturation temperature, and outlet conditions on HFO1234ze(E) boiling inside a Brazed Plate Heat Exchanger (BPHE). The effect of the heat flux on the heat transfer coefficients was remarkable. Similar consideration applies for outlet condition effects whereas the impact of saturation temperature was found to be lower. The frictional pressure drop shows a linear dependence on the refrigerant kinetic energy per unit volume. The two-phase flow boiling heat transfer coefficients were compared with a new model for refrigerant boiling inside BPHE (Longo et al., 2015): the mean absolute percentage deviation between calculated and experimental data is 7.2%. The present data points were compared with those of HFC134a and HFO1234yf previously measured inside the same BPHE under the same operating conditions: HFO1234ze(E) exhibits heat transfer coefficients very similar to HFC134a and HFO1234yf and frictional pressure drops slightly higher than HFC134a and HFO1234yf. (C) 2016 Elsevier Ltd and IIR. All rights reserved.
机译:本文研究了热流量,饱和温度和出口条件对钎焊板式换热器(BPHE)内沸腾的HFO1234ze(E)的影响。热通量对传热系数的影响是显着的。对于出口条件的影响也有类似的考虑,而饱和温度的影响被发现较低。摩擦压降对每单位体积的制冷剂动能具有线性依赖性。将两相流沸腾传热系数与BPHE内部制冷剂沸腾的新模型进行了比较(Longo等人,2015年):计算数据和实验数据之间的平均绝对百分比偏差为7.2%。将当前数据点与先前在相同操作条件下在同一BPHE中测量的HFC134a和HFO1234yf进行了比较:HFO1234ze(E)的传热系数与HFC134a和HFO1234yf非常相似,并且摩擦压降略高于HFC134a和HFO1234yf。 (C)2016 Elsevier Ltd和IIR。版权所有。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号