Effects of fan-starting methods on the reverse-cycle defrost performance of an air-to-water heat pump

机译:风机启动方式对空水热泵逆循环除霜性能的影响

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The effects of fan starting methods on the defrost performance in an air-source heat pump were investigated experimentally. Experiments were conducted on a 50 kW unitary air-to-water heat pump, The dynamic characteristics of both the coil fan pre-start and normal-start tests during the defrost cycle were discussed. The peak of discharge pressure for the fan normal-start test was up to 2595.6 kPa during defrost termination and recovery time, which was close to the discharge protection value (2650 kPa). The discharge pressure for the fan pre-start test was 742.3 kPa lower at the end of the drain time, so the peak of the discharge pressure was 687 kPa lower during the defrost termination and recovery time than that for the fan normal-start test. We found the phenomenon seemed to be related to both the small inner volume of the plate heat exchanger and larger refrigerant flow rate during the defrost termination and recovery time. Pertinent performance data (pressure, temperature, superheat, sub-cooling, etc) was plotted and discussed to determine the effects of the coil fan pre-start.
机译:实验研究了风机启动方式对空气源热泵除霜性能的影响。在一个50 kW的空气-水一体式热泵上进行了实验,讨论了除霜循环期间盘管风扇预启动和正常启动测试的动态特性。在除霜终止和恢复期间,风扇正常启动测试的排气压力峰值高达2595.6 kPa,接近排气保护值(2650 kPa)。在排空时间结束时,风扇预启动测试的排气压力降低了742.3 kPa,因此在除霜终止和恢复时间内,排气压力的峰值比风扇正常启动测试的排气压力降低了687 kPa。我们发现该现象似乎与除霜终止和恢复期间板式换热器的内部容积较小以及制冷剂流量较大有关。绘制并讨论了相关的性能数据(压力,温度,过热,过冷等),以确定线圈风扇预启动的效果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号