首页> 外文期刊>International Journal of Refrigeration >Heat and mass transfer studies on a compact bubble absorber in R134a-DMF solution based vapour absorption refrigeration system
【24h】

Heat and mass transfer studies on a compact bubble absorber in R134a-DMF solution based vapour absorption refrigeration system

机译:基于R134a-DMF溶液的蒸气吸收制冷系统中紧凑型气泡吸收器的传热和传质研究

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Experimental investigations have been carried out to study heat and mass transfer characteristics of Tetrafluoro ethane (R134a) in Dimethyl formamide (DMF) solution in a compact bubble absorber of vapour absorption refrigeration system of 1 TR capacity. Plate heat exchangers have been used as system components. Bubble absorption principle is employed in the absorber and hot water supplies heat to the generator. Effect of operating parameters such as circulation ratio, absorber and generator temperatures on heat and mass transfer effectiveness, overall heat transfer coefficient and volumetric mass transfer coefficient are investigated. It is found that heat and mass transfer effectiveness of absorber are better at lower circulation ratios and higher generator temperatures. Experimental results are compared with those obtained from numerical model developed earlier by the authors and the agreement is generally fair. From the experimental data, a correlation has been obtained for volumetric mass transfer coefficient, using multi-linear regression analysis.
机译:已经进行了实验研究,以研究在容量为1 TR的蒸汽吸收式制冷系统的紧凑型气泡吸收器中,四氟乙烷(R134a)在二甲基甲酰胺(DMF)溶液中的传热和传质特性。板式换热器已用作系统组件。吸收器采用气泡吸收原理,热水将热量提供给发生器。研究了诸如循环比,吸收塔和发生器温度等操作参数对传热和传质效率,总传热系数和体积传质系数的影响。发现在较低的循环比和较高的发电机温度下,吸收器的传热和传质效果更好。将实验结果与作者先前开发的数值模型获得的结果进行比较,并且该协议通常是公平的。从实验数据,使用多线性回归分析获得了体积传质系数的相关性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号