A transient model of airflow and heat transfer in an indoor ice rink and a quasi-steady model of its refrigeration system have been coupled and used to simulate their response to the time dependent ambient conditions and operating schedule for a typical meteorological year. The results for two different cases show that it is possible to reduce significantly the time of operation of the compressors and the energy consumption of the refrigeration system by simultaneously reducing the ceiling emissivity and increasing the secondary coolant temperature without affecting the quality of the ice.
机译:室内溜冰场中气流和热传递的瞬态模型及其制冷系统的准稳态模型已被耦合,并用于模拟它们对典型气象年对时间相关的环境条件和运行计划的响应。两种不同情况的结果表明,通过在不影响冰质的情况下同时降低天花板的发射率和提高二次冷却剂温度,可以显着减少压缩机的运行时间和制冷系统的能耗。