首页> 外文期刊>International Journal of Refrigeration >Numerical simulation of counter-flow wet-cooling towers
【24h】

Numerical simulation of counter-flow wet-cooling towers

机译:逆流湿式冷却塔的数值模拟

获取原文
获取原文并翻译 | 示例
           

摘要

Cooling towers are used to cool a warm water stream through evaporation of part of the water into an air stream. A cooling tower consists of three zones; namely spray, packing and rain zones. In cooling towers, a significant portion of the total heat rejected may occur in the spray and rain zones. These zones are modeled and solved numerically using a computer code. The developed models of these zones are validated against experimental data. For the case study under consideration, the error in calculation of the tower volume is 1.5% when the spray and rain zones are neglected. This error is reduced to 1.1% and 0.25% as the spray and rain zones are incorporated in the model, respectively. Furthermore, the effect of the Lewis factor on the performance prediction of wet-cooling towers is investigated using Bosnjakovic equation.
机译:冷却塔用于通过将一部分水蒸发成气流来冷却热水。冷却塔由三个区域组成;即喷雾区,包装区和雨区。在冷却塔中,排出的总热量的很大一部分可能发生在喷雾区和雨水区。使用计算机代码对这些区域进行建模和数值求解。这些区域的开发模型已针对实验数据进行了验证。对于正在考虑的案例研究,当忽略喷雾和雨水区时,塔体积的计算误差为1.5%。由于将雾化区和降雨区分别纳入模型中,因此该误差分别降低至1.1%和0.25%。此外,使用Bosnjakovic方程研究了Lewis因子对湿冷塔性能预测的影响。