首页> 外文期刊>International Journal of Refrigeration >Reversing air-source heat pumps - Noise at defrost initiation and a noise reducing strategy
【24h】

Reversing air-source heat pumps - Noise at defrost initiation and a noise reducing strategy

机译:反向空气源热泵-除霜启动时的噪声和降噪策略

获取原文
获取原文并翻译 | 示例
           

摘要

With the increasing use of air source heat pumps, noise disturbance can be a barrier for further market growth and acceptance. Both steady state noise level and noise events influence reported noise disturbance. In this study one of the transient noise events was investigated: the noise initiated when the heat pump shifts to defrost mode. The results show that noise from a heat pump at defrost initiation was strongly dependent on the pressure differences in the system at the time of the shift. A reduced pressure difference resulted in a lower noise level. A control strategy that adds an idling time for the heat pump just before the shift of the 4-way valve is therefore suggested. This will have a small negative effect (<3%) on the heat capacity of the heat pump but the effect upon the COP will be negligible. (C) 2016 Elsevier Ltd and International Institute of Refrigeration. All rights reserved.
机译:随着空气源热泵使用的增加,噪声干扰可能成为进一步市场增长和接受的障碍。稳态噪声水平和噪声事件都会影响所报告的噪声干扰。在这项研究中,研究了一种瞬态噪声事件:当热泵转换为除霜模式时产生的噪声。结果表明,除霜启动时来自热泵的噪声很大程度上取决于换档时系统中的压差。减小的压差导致较低的噪音水平。因此,建议采用一种控制策略,在四通阀换档之前增加热泵的空转时间。这将对热泵的热容产生较小的负面影响(<3%),但对COP的影响可忽略不计。 (C)2016 Elsevier Ltd和国际制冷学会。版权所有。