首页> 外文期刊>International Journal of Refrigeration >Experiment investigation of reverse cycle defrosting methods on air source heat pump with TXV as the throttle regulator
【24h】

Experiment investigation of reverse cycle defrosting methods on air source heat pump with TXV as the throttle regulator

机译:以TXV为节气门调节器的空气源热泵逆向循环除霜方法的实验研究。

获取原文
获取原文并翻译 | 示例
       

摘要

Reverse-cycle defrosting technique is one of the simplest and most widely used defrosting methods for air source heat pumps (ASHP). However, there are still some problems if thermal expansive valve (TXV) is used as throttle regulator in the unit: the defrosting process might last so long that users would feel uncomfortable due to the fluctuation of the indoor temperature: the system cannot resume heating mode smoothly after the defrosting process, the system often breaks down due to the triggering of low-pressure switch. In this paper the authors proposed that these two problems can be greatly relieved if there is a by-pass solenoid valve in the system which can by-pass the TXV used in the defrosting mode, and best performance can be addressed if the by-pass valve is energized during the whole defrosting process.
机译:逆循环除霜技术是空气源热泵(ASHP)最简单,使用最广泛的除霜方法之一。但是,如果将热膨胀阀(TXV)用作设备中的节流阀,则仍然存在一些问题:除霜过程可能会持续很长时间,以至于由于室内温度的波动用户会感到不舒服:系统无法恢复制热模式除霜过程顺利进行后,系统经常由于触发低压开关而崩溃。在本文中,作者提出,如果系统中有一个旁路电磁阀可以旁路除霜模式下使用的TXV,则可以大大缓解这两个问题,并且如果旁路可以解决最佳性能在整个除霜过程中,阀门通电。