Perceptions of indoor air quality associated with ventilation system types in elementary schools.

机译:小学与通风系统类型有关的室内空气质量感知。

获取原文
获取原文并翻译 | 示例
           

摘要

With the increased utilization of school buildings on a year-round basis, school indoor air quality has become a national concern. The purpose of this study was to evaluate possible associations between ventilation system type and occupant perception of indoor air quality. Staff (n = 403) from 12 schools completed a self-administered questionnaire. Carbon dioxide (CO2) levels, air exchange rates, and particle counts were also measured for each school. Schools with unit ventilator (UV) systems had the lowest mean CO2 level at 637 ppm, followed by the variable air volume (VAV) systems with 664 ppm, and constant volume (CV) systems with a mean of 703 ppm. Schools with UV systems had the lowest mean air exchange rate at 2.67 air changes per hour (ACH), followed by the VAV system type at 2.80 ACH and the CV system type at 4.61 ACH. Indoor versus outdoor particle ratios were calculated for each ventilation system type. Particles with aerodynamic diameters ranging from 0.1-1.0 microm had a geometric mean ratio ranging from 0.38 to 0.68; particles with aerodynamic diameters ranging from 1-3 microm had ratios ranging from 1.39 to 5.47, and particles with aerodynamic diameters greater than 3 microm had ratios ranging from 3.20 to 14.76. Schools using VAV systems had a significantly lower prevalence of red and watery eyes while schools with UV systems had an elevated prevalence of nasal congestion, sore throat, headache, and dustiness complaints. This increased prevalence of complaints in buildings with UV systems may be due to the increased particulate levels.
机译:随着学校建筑利用率的不断提高,学校的室内空气质量已成为全国关注的问题。这项研究的目的是评估通风系统类型与室内空气质量乘员感知之间的可能联系。来自12所学校的工作人员(n = 403)填写了一份自行管理的问卷。还为每所学校测量了二氧化碳(CO2)含量,空气交换速率和颗粒计数。装有换气设备(UV)的学校的平均CO2水平最低,为637 ppm,其次是可变风量(VAV)的系统,为664 ppm,以及定容(CV)的系统,平均为703 ppm。配备紫外线系统的学校的平均空气交换率最低,为每小时2.67空气变化量(ACH),其次是2.80 ACH的VAV系统类型和4.61 ACH的CV系统类型。计算每种通风系统类型的室内与室外颗粒比。空气动力学直径为0.1-1.0微米的颗粒的几何平均比为0.38至0.68;空气动力学直径为1-3微米的颗粒的比率为1.39至5.47,空气动力学直径大于3微米的颗粒的比率为3.20至14.76。使用VAV系统的学校红眼和水汪汪的患病率显着降低,而使用UV系统的学校鼻塞,喉咙痛,头痛和尘土飞扬的患病率较高。在装有紫外线系统的建筑物中,这种抱怨的增加可能是由于颗粒物含量的增加。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号