Investigation of heat exchanger inclination in forced-draught air-cooled heat exchangers

机译:强制通风风冷换热器的换热器倾角研究

获取原文
获取原文并翻译 | 示例

摘要

The purpose of this study is to determine the influence of inclining the heat exchanger relative to the fan in a forced draught air-cooled heat exchanger. Since inclination increases plenum depth, the effect of inclination is also compared with increasing plenum depth without inclination. The experimental study shows that inclination improves thermal performance by only 0.5%, when compared with a baseline non-inclined case with a shallow plenum. Similarly, increasing plenum depth without inclination has a thermal performance benefit of approximately 1%. The numerical study shows that, as the heat exchanger is inclined, the low velocity core at the centre of the heat exchanger moves to one side.
机译:这项研究的目的是确定在强制通风的空气冷却式热交换器中,使热交换器相对于风扇倾斜的影响。由于倾斜增加了气室深度,因此倾斜的效果也与不倾斜增加气室深度进行了比较。实验研究表明,与基线浅层通风不倾斜的情况相比,倾斜仅可将热性能提高0.5%。类似地,增加气室深度而不倾斜会带来大约1%的热性能优势。数值研究表明,当热交换器倾斜时,位于热交换器中心的低速堆芯向一侧移动。