首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Airflow maldistribution and the performance of a packaged air conditioning unit evaporator
【24h】

Airflow maldistribution and the performance of a packaged air conditioning unit evaporator

机译:气流分布不均和整套空调机组蒸发器的性能

获取原文
获取原文并翻译 | 示例
       

摘要

The performance of an evaporator for a packaged air conditioning unit has been investigated. A heat transfer program ACOL5 validated in an earlier study, was used to predict the performance. Nonuniform velocity distribution measurements taken in a typical air conditioning unit were employed in the prediction of the evaporator performance. It was found that this maldistribution reduced the performance of an evaporator circuit, as compared to uniform flow. Circuits at the edges of the evaporator, where the velocity was low, did not perform well. With the refrigerants controlled by one thermostatic value, the worst performing circuit affected the performance of the whole evaporator, the evaporator performance being reduced by as much as 35%. The performance of the evaporator, where the circuits had different numbers of passes, depended on the position of the circuit in the evaporator.
机译:已经研究了用于成套空调装置的蒸发器的性能。在较早的研究中验证过的传热程序ACOL5用于预测性能。在典型的空调装置中进行的非均匀速度分布测量被用于预测蒸发器性能。已经发现,与均匀流动相比,这种分布不均降低了蒸发器回路的性能。速度低的蒸发器边缘的电路性能不佳。在制冷剂被一个恒温值控制的情况下,性能最差的回路影响了整个蒸发器的性能,蒸发器性能降低了35%之多。回路的通过次数不同时,蒸发器的性能取决于回路在蒸发器中的位置。