首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >New method for measuring field performance of variable refrigerant flow systems based on compressor set energy conservation
【24h】

New method for measuring field performance of variable refrigerant flow systems based on compressor set energy conservation

机译:基于压缩机集节能测量的可变制冷剂流量系统现场性能的新方法

获取原文
获取原文并翻译 | 示例
           

摘要

In recent years, variable refrigerant flow (VRF) systems have gained popularity in commercial and residential buildings. It is extremely significant to obtain the real performance of VRF systems in order to improve design. However, the measurement of the field cooling or heating capacity of air-cooled VRF systems has not yet been thoroughly addressed. In this paper, a novel field measurement method for the capacity of VRF systems is proposed based on the energy conservation of a compressor set. The compressor set consists of the actual compressor, oil separator, and capillary with the corresponding pipelines. The validation results indicate that the compressor set energy conservation method yields 15% accuracy for cooling capacity and 13% accuracy for heating capacity. Furthermore, the novel measurement method was applied to a VRF system in an office building over four weeks during the heating season. The field test results demonstrate that the average part-load ratio of the VRF system was 0.33, which revealed that the sizing of the VRF system was relatively excessive.
机译:近年来,可变制冷剂流(VRF)系统在商业和住宅建筑中获得了普及。获得VRF系统的实际性能是非常重要的,以改善设计。然而,尚未彻底解决空气冷却的VRF系统的现场冷却或加热容量的测量。本文基于压缩机集的节能提出了一种用于VRF系统容量的新颖场测量方法。压缩机组包括实际压缩机,油分离器和具有相应管道的毛细管。验证结果表明,压缩机设定节能法为冷却能力和加热能力精度13%的精度产生15%的精度。此外,在加热季节4周内,将新的测量方法应用于办公大楼的VRF系统。现场测试结果表明,VRF系统的平均载荷比为0.33,表明VRF系统的尺寸相对过多。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号