摘要

HighlightsThe effect of descaling device to fouling resistance outside tubes is investigated.Paper focus on the surface where spray water evaporate into air.The microstructure of the dirt sample is analyzed by SEM.The reason for “secondary descaling” is given.Giving reason for descaling effect reduced sequentially in each descaling stage.AbstractUnder actual operating conditions, a closed cooling tower was simulated and an experimental study conducted to determine the descaling characteristics of an induction-type electronic descaling device on the spray water side of an evaporative cooler. After a long period of experimental observation and analysis, the results show that: an induction-type electronic descaling device on the outside of the heat pipe can accelerate the dissolution of dirt and reduce fouling resistance. During the 160h of the experiment, reduction of fouling resistance occurred several times. At the end of each descaling stage, the fouling resistance was reduced by 20.35%, 3.27% and ?0.22% compared with the fouling resistance at the beginning of the experiment. SEM (Scanning Electron Microscope) revealed that the dirt crystal was primarily block structure, the dense layer was thin and the overall structure was loose.]]>
机译:<![cdata [ 亮点 研究了除垢装置对污垢的抗污染外部管道的效果。 纸张专注于表面上的纸张喷水蒸发到空气中。 通过SEM分析污垢样本的微观结构。 给出“次级除垢”的原因。 在每个除垢阶段中依次减少除垢效果的原因。 抽象 在实际操作条件下,模拟封闭的冷却塔,并进行实验研究,以确定蒸发冷却器的喷水侧上的感应型电子除垢装置的除垢特性。经过长时间的实验观察和分析,结果表明:热管外侧的感应型电子除垢装置可以加速污垢的溶解并减少污垢阻力。在实验的160小时期间,减少污垢抗性发生了几次。在每个除垢阶段结束时,与实验开始时的污垢阻力相比,污垢抗性降低了20.35%,3.27%,3.27%。 SEM(扫描电子显微镜)显示污垢晶体主要是块结构,致密层薄,整体结构松散。 ]]>

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号