Improvement of NH_3 Gas Analyzer for ESP Outlet and Application of Analyzer for NH_3 Gas Injection Control

机译:NH_3 气体分析仪 的改进 ESP 出口 和 分析仪的应用 为 NH_3 注气控制

获取原文
获取原文并翻译 | 示例
           

摘要

The NH_3 ESP outlet flue gas analyzer wasassumed not to be applicable to an NH_3 injection feedbackcontrol. Because it has a late response to changing boiler loadand NH_3 concentration in flue gas, and due to decreasedanalysis accuracy in operation. MHI and Shimazu Corporation,the manufacturer of the gas analyzer, clarified that the gassampling probe caused the problem, and have been developing anew probe. Based on field tests, we confirmed that the newprobe improves response time and analyzer accuracy. We alsodeveloped new feedback control for NH_3 ESP gas injection forusing the new probe. The first system was delivered to TokyoElectric Power Company, and is currently operating without problems.
机译:NH_3 ESP出口烟道气体分析仪不适用于NH_3注射送料CONCOROL。 因为它对烟道气中的改变锅炉载荷和NH_3浓度有了后期反应,并且由于操作中的减少精度。 MHI和Shimazu Corporation是天然气分析仪的制造商,澄清了Gassampling探针引起了问题,并且一直在开发探针。 基于现场测试,我们确认NewProbe提高了响应时间和分析器的准确性。 我们为NH_3 ESP气体注射挖掘新探头的新反馈控制。 第一个系统被交给东京电力公司,目前没有问题运行。