Improvement of NH_3 Gas Analyzer for ESP Outlet and Application of Analyzer for NH_3 Gas Injection Control

机译:ESP出口NH_3气体分析仪的改进和NH_3气体注入控制分析仪的应用

获取原文
获取原文并翻译 | 示例
           

摘要

The NH_3 ESP outlet flue gas analyzer wasassumed not to be applicable to an NH_3 injection feedbackcontrol. Because it has a late response to changing boiler loadand NH_3 concentration in flue gas, and due to decreasedanalysis accuracy in operation. MHI and Shimazu Corporation,the manufacturer of the gas analyzer, clarified that the gassampling probe caused the problem, and have been developing anew probe. Based on field tests, we confirmed that the newprobe improves response time and analyzer accuracy. We alsodeveloped new feedback control for NH_3 ESP gas injection forusing the new probe. The first system was delivered to TokyoElectric Power Company, and is currently operating without problems.
机译:假设NH_3 ESP出口烟气分析仪不适用于NH_3注入反馈控制。因为它对锅炉负荷的变化和烟气中NH_3的浓度具有较晚的响应,并且由于运行中的分析精度降低而导致。 MHI和气体分析仪制造商Shimazu Corporation澄清说,气体采样探头引起了问题,并且正在开发新的探头。根据现场测试,我们证实了该新探针可改善响应时间和分析仪精度。我们还使用新探头开发了用于NH_3 ESP气体注入的新反馈控制。第一个系统交付给东京电力公司,并且目前运行正常。