首页> 外文期刊>Journal of Performance of Constructed Facilities >Seismic Analysis of a 500-kV Power Transformer of the Type Damaged in the 2008 Wenchuan Earthquake
【24h】

Seismic Analysis of a 500-kV Power Transformer of the Type Damaged in the 2008 Wenchuan Earthquake

机译:2008年汶川地震损坏的500 kV电力变压器的地震分析

获取原文
获取原文并翻译 | 示例
           

摘要

As indispensable electric power equipment in substations, high-voltage power transformers have experienced severe damage in past earthquakes. This paper illustrates an earthquake-damaged 500-kV power transformer: all three 550-kV bushings fractured, oil conservator supports were sheared off, and leaked transformer oil caused a fire. A detailed finite-element model of the power transformer was developed. The modal and response-history analyses using the finite-element model were conducted to investigate possible reasons for the power transformer earthquake damage. The results indicated that the local modes of the transformer components, such as bushings and turrets, and the oil conservator dominate the power transformer vibration. Spectral accelerations at the top flange plates of the turrets on the transformer tank were significantly amplified for the transformer bushings. Peak resultant bending moments at the bottoms of the air-side insulators of the 550-kV bushings subjected to the Wenchuan earthquake motions exceeded their bending capacities. Accelerations for the oil conservator were also greatly amplified, thus the oil conservator supports suffered large translational and torsional deformations to the earthquake motions. It is concluded from the earthquake damage and seismic analyses that this type of power transformer is vulnerable to strong earthquakes because the earthquake effect is not adequately considered in the power transformer structural design. (C) 2018 American Society of Civil Engineers.
机译:作为变电站中不可缺少的电力设备,高压电力变压器在过去的地震中经历过严重损坏。本文说明了地震损坏的500 kV电力变压器:所有三个550 kV衬套破裂,剪切漏油机支架,泄漏的变压器油导致火灾。开发了一种电力变压器的详细有限元模型。进行了使用有限元模型的模态和响应历史分析,以研究电力变压器地震损坏的可能原因。结果表明,变压器部件的局部模式,如衬套和炮塔,以及储油器占据了电力变压器振动。变压器衬套上炮塔上的炮塔顶部凸缘板的光谱加速度显着放大。 550-KV衬套的空气侧绝缘子底部底部的峰值得到的弯曲力矩超过了汶川地震运动的弯曲能力。石油保图的加速度也大大放大,因此石油保护员支撑遭受大型平移和扭转变形的地震运动。从地震损伤和地震分析中得出结论,这种类型的电力变压器容易受到强烈地震的影响,因为电力变压器结构设计中没有充分考虑地震效果。 (c)2018年美国土木工程师协会。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号