DC Fault Current Clearance at the Source Side of HVDC Grid Using Hybrid MMC

机译:使用混合MMC的HVDC网格源极侧的DC故障电流间隙

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

This paper proposes a source-side DC fault current clearance scheme for HVDC grids under DC short-circuit faults. The scheme uses half-bridge submodules (HBSM) and full-bridge submodules (FBSMs)-based hybrid modular multilevel converter (MMC). The DC fault current behaviors of the HVDC grid is revealed as a primary criterion for the proposed approach. The additional degrees-of-freedom for control of hybrid MMC are incorporated into the HVDC grid to interrupt the fault current feeding at the source side. During the fault ride-through process, the reactive power compensation is maintained. The proposed method does not need the DC circuit breakers since the current in the fault line can be controlled to zero. The primary and backup protection schemes for hybrid MMC-HVDC grid are proposed. The effectiveness of the method is validated by electromagnetic transient simulations on PSCAD/EMTDC.
机译:本文提出了DC短路故障下的HVDC网格源侧DC故障电流清除方案。 该方案采用半桥子模块(HBSM)和全桥柱(FBSMS)的混合模块化多级转换器(MMC)。 HVDC网格的DC故障电流行为作为所提出的方法的主要标准揭示。 控制混合MMC的额外自由度并入到HVDC网格中,以中断源侧的故障电流。 在故障驾驶过程中,保持无功补偿。 所提出的方法不需要DC断路器,因为故障线中的电流可以被控制为零。 提出了用于混合MMC-HVDC网格的主要和备用保护方案。 PSCAD / EMTDC的电磁瞬态仿真验证了该方法的有效性。