Investigation of Diagnostic Technique for Thermal Fault on Natural Ester Oil-immersed Transformer by Dissolved Gas Analysis

机译:溶解气体分析对天然酯油浸没式变压器热故障诊断技术研究

获取原文
获取原文并翻译 | 示例
           

摘要

Dissolved Gas Analysis (DGA) of insulating oil has been widely used as an essential diagnostic technique for condition assessment of oil-immersed transformer's. Many researches and investigations have been reported for the DGA of mineral oil-immersedtransformers and guidelines have been proposed to assess the condition of oil-immersed transformers in the world. Recently transformers using alternative insulating oil such as natural ester oil have been installed extensively because of its good environmental andfire safety aspect such as biodegradation, carbon-neutral and high flash point. Consequently there is an increasing demand for the diagnostic techniques and guidelines for DGA of the natural ester oil-immersed transformers.This paper describes the behaviour of gas generation obtained by heating test of natural ester oil simulating thermalfault of natural ester oil-immersed transformer. Natural ester oil were continuously heatedfor 10 minutes at the temperature from 100°Cup to 900°C with the step of 100°G After the heating tests, combustible gases such as hydrogen, methane, ethylene, acetylene and ethane were detected and the correlation was observed between heating temperature and concentration ratio of decomposed gases.Further improvement of the accuracy of estimation of overheating temperature, a diagnosis map using a combination of multiple ratios of gas concentrations is also commonly used for diagnosis of thermal fault. The diagnosis maps selectedfrom combination of gas including acetylene are most effective diagnosis map to diagnose overheating temperature of ester oil-immersed transformer. Even in case when acetylene is not detected or high concentration of hydrogen only detected such as Stray Gassing, the overheating temperature of natural ester oil-immersed transformer can be estimated by using the diagnosis map with another indicator gas not using acetylene or hydrogen.
机译:绝缘油的溶解气体分析(DGA)已被广泛用作油浸式变压器条件评估的基本诊断技术。据报道,矿物油浸没器的DGA的许多研究和调查已经提出了准则,以评估世界上的油浸式变压器的状况。最近使用替代绝缘油的变压器,如天然酯油,由于其良好的环境和最高的安全方面,如生物降解,碳中性和高闪点。因此,对天然酯油浸式变压器的DGA诊断技术和指南的需求越来越大。本文描述了通过加热天然酯油模拟热弹性的天然酯油浸渍式变压器的加热试验所获得的气体产生的行为。在加热试验之后,在100°G的步骤中,在100°G的步骤中,在100°G的步骤中连续加热天然酯油10分钟,检测诸如氢气,甲烷,乙烯,乙炔和乙烷的可燃气体并进行相关性在分解气体的加热温度和浓度比之间观察到。改善过热估计的准确性,使用多种气体浓度的组合的诊断图也通常用于诊断热故障。从包括乙炔的气体组合的诊断图是最有效的诊断图,以诊断酯油浸式变压器的过热温度。即使如果没有检测到乙炔或仅检测到诸如杂散的诸如杂散的脂肪浓度的氢气,则可以通过使用不使用乙炔或氢气的另一种指示气体的诊断图来估算天然酯油浸渍的变压器的过热温度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号