摘要

The single-phase voltage loss is a common fault. Once the voltage-loss failure occurs, the amount of electrical energy will not be measured, but it is to be calculated so as to protect the interest of the power supplier. Two automatic calculation methods, the power substitution and the voltage substitution, are introduced in this paper. Considering the lack of quantitative analysis of the calculation error of the voltage substitution method, the grid traversal method and MATLAB tool are applied to solve the problem. The theoretical analysis indicates that the calculation error is closely related to the voltage unbalance factor and the power factor, and the maximum calculation error is about 6% when the power system operates normally. To verify the theoretical analysis, two three-phase electrical energy metering devices have been developed, and verification tests have been carried out in both the lab and field conditions. The lab testing results are consistent with the theoretical ones, and the field testing results show that the calculation errors are generally below 0.2%, that is correct in most cases.
机译:单相电压损耗是常见故障。一旦发生电压损耗,就不会测量电能量,但要计算出来以保护电源供应商的兴趣。本文介绍了两种自动计算方法,电力替换和电压替代。考虑到缺乏对电压替换方法的计算误差的定量分析,应用了网格遍历方法和MATLAB工具来解决问题。理论分析表明,计算误差与电压不平衡因子和功率因数密切相关,当电力系统正常运行时,最大计算误差约为6%。为了验证理论分析,已经开发了两个三相电能计量装置,并且在实验室和现场条件下进行了验证测试。实验室测试结果与理论上一致,现场测试结果表明,在大多数情况下,计算误差通常低于0.2%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号