首页> 外文期刊>Engineering failure analysis >Snubber resistor influence in the thyristor valves failure on the static VAR compensator
【24h】

Snubber resistor influence in the thyristor valves failure on the static VAR compensator

机译:缓冲电阻在静态VAR补偿器上的晶闸管阀门的影响

获取原文
获取原文并翻译 | 示例
           

摘要

In this research, a complex engineering failure analysis is done for a static VAR compensator (SVC), it was installed in Peru 220 kV system. The research introduce the selected results of the simulations and field tests completed during the fault, mitigation and corrective activities performed at the thyristor valve, which is installed in the thyristor switched capacitor (TSC) and thyristor controlled reactor (TCR) of the SVC. This paper proposes the most feasible solution to overcome the failure of the TSC based on snubber resistor in the SVC. In order to investigate the causes of this failure, various measurements were carried out on the TSC. It was concluded that a snubber resistor design needs two special test for determinate a problem or abnormal condition; a special test should be done in the factory acceptance test (FAT), site acceptance test (SAT) and to execute a maintenance diagnosis, to prevent a failure in the thyristor valve from TSC. This failure has happened in the standby system, the susceptance reference is forced to follow the susceptance reference received from the active system. There is however, a delay in the transfer of data from the active to the standby system. During transient conditions this may cause a difference in thyristor firing angles between the systems. The simulated current in the standby system does not agree with the measured current, which is controlled by the active system, an advanced diagnosis and design review is developed for to avoid a sudden failure. The feasibility of these solutions was verified through the computer simulation with PSCAD/EMTDC.
机译:在本研究中,为静态VAR补偿器(SVC)进行了复杂的工程故障分析,它安装在秘鲁220 kV系统中。该研究介绍了在晶闸管阀门执行的故障,缓解和纠正活动期间完成的模拟和现场测试的所选结果,该阀门安装在SVC的晶闸管开关电容(TSC)和晶闸管控制的反应器(TCR)中。本文提出了最可行的解决方案来克服SVC中的缓冲电阻的TSC失效。为了研究这种失败的原因,在TSC上进行各种测量。结论是,缓冲电阻设计需要两个特殊测试来确定问题或异常情况;应在工厂验收测试(FAT)中进行特殊测试,网站验收测试(SAT)并执行维护诊断,防止晶闸管阀从TSC进行故障。这种故障发生在备用系统中,掌管参考被强制遵循从主动系统接收的基准。然而,存在从活动到备用系统的数据传输数据的延迟。在瞬态条件下,这可能导致系统之间的晶闸管触发角差异。备用系统中的模拟电流与测量的电流同意,由主动系统控制,开发了先进的诊断和设计评审,以避免突然发生故障。通过使用PSCAD / EMTDC的计算机模拟验证了这些解决方案的可行性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号