Failure analysis of a plate heat exchanger used in a blast chiller

机译:爆破冷却器中使用的板式换热器的故障分析

获取原文
获取原文并翻译 | 示例
       

摘要

A stainless steel plate heat exchanger (PHE) was received to investigate the cause of its perforation in service leading to mixing of the fluids (water and refrigerant) circulating in the system. The heat exchanger was employed in a blast chiller using seawater subjected to a reverse osmosis process followed by salinization and sanitizing treatments. This study includes the analysis of water samples in different points of the system, a metallurgical characterization of the material of the plates, a study of the composition of corrosion products and an evaluation of the electrochemical behaviour of the material in the water samples extracted from the system. The study revealed that the material of the plates was perforated by a corrosion process due to the high level of chlorides present in the water employed in the blast chiller. Moreover, the localized attack of the stainless steel plates is enhanced by the peculiar geometry of the heat exchanger that leads to crevice corrosion in the region of the joint between overlapping plates. The results obtained in this work indicate that the failure is associated to the water treatment process performed upstream of the heat exchanger.
机译:收到不锈钢板换热器(PHE)以研究其穿孔的养护原因,导致在系统中循环的流体(水和制冷剂)混合。使用经受反渗透过程的海水采用热交换器在爆破冷却器中使用,然后进行盐渍化和消毒处理。本研究包括对系统不同点的水样的分析,冶金表征板材的材料,研究了腐蚀产物的组成以及从中提取的水样中的材料的电化学行为的评价。系统。该研究表明,由于在爆破冷却器中使用的水中存在的高水平氯化物,板的材料通过腐蚀过程穿孔。此外,通过热交换器的特殊几何形状增强了不锈钢板的局部攻击,其导致在重叠板之间的接头区域中的缝隙腐蚀。在该工作中获得的结果表明失败与在热交换器上游进行的水处理过程相关联。

著录项

  • 来源
    《Engineering failure analysis》 |2018年第2018期|共12页
  • 作者单位

    Univ Udine Polytech Dept Engn &

    Architecture Via Cotonificio 108 I-33100 Udine Italy;

    Univ Udine Polytech Dept Engn &

    Architecture Via Cotonificio 108 I-33100 Udine Italy;

    Res Hub Electrolux Profess Viale Treviso 15 I-33170 Pordenone Italy;

    Res Hub Electrolux Profess Viale Treviso 15 I-33170 Pordenone Italy;

    Univ Udine Polytech Dept Engn &

    Architecture Via Cotonificio 108 I-33100 Udine Italy;

    Univ Udine Polytech Dept Engn &

    Architecture Via Cotonificio 108 I-33100 Udine Italy;

    Univ Udine Polytech Dept Engn &

    Architecture Via Cotonificio 108 I-33100 Udine Italy;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 工程力学;
  • 关键词

    Heat-exchanger; Stainless steel; Localized corrosion; Chloride;

    机译:热交换器;不锈钢;局部腐蚀;氯化物;
  • 入库时间 2022-08-20 02:38:55

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号