Transformer insulation oil CO and CO2 concentrations

机译:变压器绝缘油CO和CO2浓度

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Around the world, maintenance teams have noticed increased and further increasing CO and CO2 levels in their transformer fleet. Papers and reports have been published explaining the reason for this recent trend. This paper will provide some additional information from studies and fleet comparison. Unfortunately, new IEEE / IEC guides do not consider the latest findings. This will lead to confusion for the oil analysis laboratories and the transformer operators. Oil analyses have found transformers with more than 2,000 ppm CO which are in perfect condition This is because, as described in many publications and IEEE / IEC guides, CO and CO2 levels do not matter as long as no other gases are out of range.
机译:在世界各地,维护团队已经注意到变压器舰队中的CO和CO2水平增加,进一步增加。 论文和报告已被公布,解释了这一趋势的原因。 本文将提供研究和舰队比较的一些额外信息。 不幸的是,新的IEEE / IEC指南不考虑最新的调查结果。 这将导致油分析实验室和变压器运营商的混淆。 石油分析找到了具有超过2,000ppm的变压器,这是完美的条件,这是因为,如许多出版物和IEEE / IEC指南中所述,只要没有其他气体超出范围,CO和CO2水平就无关紧要。