首页> 外文期刊>日本冷凍空調学会論文集 >Effect of fin geometry on condensation of R134a in a staggered bundle of horizontal finned tubes
【24h】

Effect of fin geometry on condensation of R134a in a staggered bundle of horizontal finned tubes

机译:翅片几何形状对水平翅片管交错排列中R134a冷凝的影响

获取原文
获取原文并翻译 | 示例

摘要

Experimental results are presented that show the effect of fin geometry on condensation of refrigerant R134a in a staggered bundle of horizontal finned tubes. Two kinds of conventional low-fin tubes and three kinds of three-dimensional fin tubes were tested. The refrigerant mass velocity ranged from 8 to 23 kg/m{sup}2s and the condensation temperature difference from 1.5 to 12 K. In most cases, the highest performance was obtained by one of the three-dimensional fin tubes. In the case of high mass velocity and high film Reynolds number, however, the highest performance was obtained by one of the low-fin tubes. The results were compared with previous experimental results for bundles of smooth tubes and low-fin tubes.
机译:实验结果表明,翅片的几何形状对水平翅片管交错排列的制冷剂R134a的冷凝有影响。测试了两种常规的低翅片管和三种三维翅片管。制冷剂质量速度在8到23 kg / m {sup} 2s的范围内,冷凝温度差在1.5到12K。在大多数情况下,其中一个三维翅片管可获得最高的性能。然而,在高质量速度和高薄膜雷诺数的情况下,通过低翅片管之一可获得最高的性能。将结果与以前的光滑管束和低翅片管束实验结果进行比较。