摘要

Based On the heat conduction equation, fluid flow governing equation and radiation heat transfer equation, the multi-physics coupled mathematical model is established, the convection heat transfer problem between solid and fluid is solved by wall function, the three dimensional thermal and fluid fields of 27.5kV GIS which is used in the distribution system of high-speed railway are calculated and analyzed by the finite volume method. The result shows that the three-position isolation switch in the GIS is the hottest. The computed temperature rises have good agreement with the tested ones; it can prove that this mathematical model and numerical method are reasonable.
机译:基于热传导方程,流体流控制方程和辐射传热方程,建立了多物理场耦合数学模型,利用壁函数,三维热流场解决了固液对流换热问题。通过有限体积法计算分析了用于高速铁路配电系统的27.5kV GIS。结果表明,GIS中的三位置隔离开关是最热的。计算出的温度升高与测试温度有很好的一致性;可以证明该数学模型和数值方法是合理的。