首页> 外文期刊>Journal of Wind Engineering and Industrial Aerodynamics: The Journal of the International Association for Wind Engineering >Full-scale measurements of wind-induced vibration of a transmission line system in a mountainous area
【24h】

Full-scale measurements of wind-induced vibration of a transmission line system in a mountainous area

机译:山区输电线系统风致振动的满量程测量

获取原文
获取原文并翻译 | 示例
           

摘要

This paper clarifies the characteristics of wind and wind-induced vibration of an electrical transmission tower installed on a mountainous area, based on full-scale data obtained at wind speed of less than 25 m/s. The data was collected between 1991 and 1993. As a result, it can clearly be seen that difference of wind direction has a strong influence on wind characteristics. The vibration characteristics of the tower with conductors are strongly influenced by the behavior of the conductors. The aerodynamic damping of the conductors plays an important role in their total damping. The response values for acceleration, strain of the tower with conductors, and tensile forces of conductors increase in proportion to the power of the wind speed. In general, the value of each power index is less than 2.
机译:本文基于风速小于25 m / s时获得的满量程数据,阐明了安装在山区的输电塔的风和风振特性。数据是在1991年至1993年之间收集的。因此,可以清楚地看到,风向的差异对风的特性有很大的影响。带有导体的塔架的振动特性受导体性能的强烈影响。导体的空气动力学阻尼在其总阻尼中起着重要的作用。加速度,带有导体的塔架应变以及导体的拉力的响应值与风速的功率成比例地增加。通常,每个功率指标的值都小于2。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号