Waste Heat Recovery in Data Centers Using Sorption Systems

机译:使用吸附系统回收数据中心中的废热

获取原文
获取原文并翻译 | 示例
       

摘要

Of the total electricity consumption by the United States in 2006, more than 1% was used on data centers alone; a value that continues to rise rapidly. Of the total amount of electricity a data center consumes, about 30% is used to cool server equipment. The present study conceptualizes and analyzes a novel paradigm consisting of integrated power, cooling, and waste heat recovery and upgrade systems that considerably lower the energy footprint of data centers. Thus, on-site power generation equipment is used to supply primary electricity needs of the data center. The microturbine-derived waste heat is recovered to run an absorption chiller that supplies the entire cooling load of the data center; essentially providing the requisite cooling without any additional expenditure of primary energy. Furthermore, the remaining waste heat rejected by the data center is boosted to a higher temperature with a heat transformer; with the upgraded thermal stream serving as an additional output of the data center with negligible additional electrical power input. Such upgraded heat can be used for district heating applications in neighboring residential or commercial buildings, or as process heat for commercial end uses such as laundries, hospitals, and restaurants, depending on the location of the data center. With such a system, the primary energy usage of the data center as a whole can be reduced by up to 23% while still addressing the high-flux cooling loads, in addition to providing a new income stream through the sales of upgraded thermal energy, Given the large and fast-escalating energy consumption patterns of data centers, this novel, integrated approach to electricity and cooling supply, and waste heat recovery and upgrade will substantially reduce primary energy consumption for this important end use worldwide.
机译:在2006年美国的总电力消耗中,仅数据中心的电力消耗就超过1%。持续快速增长的价值。数据中心消耗的总电量中,约有30%用于冷却服务器设备。本研究概念化并分析了一种新颖的范例,该范例由集成的电源,冷却以及废热回收和升级系统组成,可大大降低数据中心的能耗。因此,现场发电设备用于满足数据中心的主要电力需求。回收来自微型涡轮机的废热,以运行吸收式制冷机,该制冷机可为数据中心提供整个制冷负载。本质上提供了必要的冷却,而没有任何额外的一次能源消耗。此外,通过热转换器将数据中心排出的剩余废热提高到更高的温度;升级后的热流可以用作数据中心的附加输出,而附加的电力输入可以忽略不计。根据数据中心的位置,这种提高的热量可用于相邻住宅或商业建筑中的区域供热应用,或作为商业最终用途(如洗衣店,医院和饭店)的过程供热。借助这样的系统,除了通过销售升级后的热能提供新的收入来源外,整个数据中心的一次能源使用量最多可减少23%,同时仍可解决高流量的冷却负荷问题,鉴于数据中心的能耗模式正在迅速扩大,这种新颖的电力和制冷供应,废热回收和升级的集成方法将大大降低全球这一重要最终用途的一次能源消耗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号