首页> 外文期刊>Journal of Mechanical Science and Technology >Thermal performance analysis of heat exchanger for closed wet cooling tower using heat and mass transfer analogy
【24h】

Thermal performance analysis of heat exchanger for closed wet cooling tower using heat and mass transfer analogy

机译:基于传热传质的闭式湿式冷却塔换热器热性能分析

获取原文
获取原文并翻译 | 示例
           

摘要

In closed wet cooling towers, the heat transfer between the air and external tube surfaces can be composed of the sensible heat transfer and the latent heat transfer. The heat transfer coefficient can be obtained from the equation for external heat transfer of tube banks. According to experimental data, the mass transfer coefficient was affected by the air velocity and spray water flow rate. This study provides the correlation equation for mass transfer coefficient based on the analogy of the heat and mass transfer and the experimental data. The results from this correlation equation showed fairly good agreement with experimental data. The cooling capacity and thermal efficiency of the closed wet cooling tower were calculated from the correlation equation to analyze the performance of heat exchanger for the tower.
机译:在封闭的湿式冷却塔中,空气和外管表面之间的热传递可以由显热传递和潜热传递组成。传热系数可以从管束外部传热的方程式获得。根据实验数据,传质系数受空气速度和喷雾水流速的影响。本研究基于传热传质和实验数据的相似性,提供了传质系数的相关方程。该相关方程的结果表明与实验数据相当吻合。根据相关方程计算出封闭式湿式冷却塔的制冷量和热效率,以分析该塔的热交换器的性能。