We present the influence of the cooling tower airflow inlet region modifications at the Sostanj 4 thermal power plant on cooling tower local efficiency. Local efficiency change was estimated based on temperature fields of drift eliminators before and after the reconstruction of the cooling tower. Temperature fields were measured with thermal vision method. The local reduction of cooling tower efficiency was analyzed based on phenomenological relations of heat transfer obtained from the selected vertical segment of the cooling tower. The characteristic influence that the reconstruction had on the temperature field was detected on the circumference of the cooling tower. The efficiency reduction was the highest on the periphery of the cooling tower and in particular section it peaked at 2%, while in most part of the area it was below 0.5%. The presented measurement and analysis method enables the estimation of changes in the local efficiency of heat transfer in cooling towers.
机译:我们介绍了Sostanj 4热电厂的冷却塔气流入口区域修改对冷却塔局部效率的影响。基于冷却塔改造前后的除水器温度场,估算了局部效率变化。用热视觉法测量温度场。根据从冷却塔的选定垂直段获得的传热现象学关系,分析了冷却塔效率的局部降低。在冷却塔的圆周上检测到重建对温度场的特性影响。在冷却塔的外围,效率降低最高,特别是在截面上达到2%的峰值,而在大部分区域则低于0.5%。提出的测量和分析方法能够估算冷却塔中局部传热效率的变化。