This study demonstrated the use of metallographic analysis and NIST's Fire Dynamics Simulator (FDS) program to identify the cause of an actual electrical fire. A severely carbonized steel plate and a cable with a bead were found inside a damaged switchboard from the debris of a factory fire. By metallographic analysis, the copper spatter on the steel plate was found to imply a short circuit has occurred and that this was the probable ignition source of the fire was supported by the presence of a small amount of copper oxide and by the cavities with the tree-like grain microstructures in the bead. The heat estimated to have been released per unit area of the switchboard in question (approximately 236.29 MJ/m(2)) served as key input data for applying the FDS simulation of the blaze. The simulation indicated that thermal insulation polyethylene (PE) played an important role in the rapid fire spread.
机译:这项研究证明了使用金相分析和NIST的火灾动力学模拟器(FDS)程序来识别实际电气火灾的原因。在工厂配电盘中,由于工厂火灾的残骸,发现了一块严重碳化的钢板和一条带珠的电缆。通过金相分析,发现钢板上的铜飞溅表明发生了短路,这是可能的火源,这是由少量氧化铜的存在和树洞引起的。珠中类似晶粒的微结构。估计所讨论的配电板每单位面积释放的热量(约236.29 MJ / m(2))用作应用FDS模拟火焰的关键输入数据。模拟表明,绝热聚乙烯(PE)在迅速蔓延的火灾中发挥了重要作用。