首页> 外文期刊>WSEAS Transactions on Fluid Mechanics >Thermostatic mixing valves - A method for non-disturbing intra-valve heat transfer estimation
【24h】

Thermostatic mixing valves - A method for non-disturbing intra-valve heat transfer estimation

机译:恒温混合阀-一种不干扰阀内传热的方法

获取原文
获取原文并翻译 | 示例
       

摘要

The time dependent control characteristics of thermostatic mixing valves are determined by the steep velocity, pressure and temperature gradients present inside the valve. The aim of this study is to investigate how these parameters affect the heat flux from the flowing water to the thermostat which both senses and realizes the control of the valve. A newly developed method for non-disturbing intra-valve measurement is used to determine the convective heat transfer coefficient (h) at the surface of the thermostat, Despite the steep gradients inside the valve, the method manages to dissolve the axial and azimuthal dependence of h. The variations are of such a magnitude that they should be accounted for when analyzing this type of valve.
机译:恒温混合阀的随时间变化的控制特性取决于阀内的陡峭速度,压力和温度梯度。这项研究的目的是研究这些参数如何影响从流水到恒温器的热通量,从而同时感测和实现阀门的控制。一种新开发的无扰动阀内测量方法可用于确定恒温器表面的对流传热系数(h),尽管阀内部存在陡峭的梯度,该方法仍能解决轴向和方位角的依赖性。 H。这些变化的幅度很大,在分析这种类型的阀门时应予以考虑。